• $100000

6kV/560-6600kw General Medium Voltage Drive

Hiconics’s medium voltage drive has new cabinet type and power-cell structure and smaller volume. The power unit and transformer are arranged in front and back, with compact structure. Through thermal analysis design, on-site installation costs and infrastructure costs can both be reduced on the basis of ensuring heat dissipation.

Technical Parameters of 6kV/560~6600kW General Medium Voltage Drive

Voltage

Motor Power(KW)

Output Capacity(KVA)

Model

Weight

(kg)

Dimension

(W*H*D)

Cabinet Type

6kV

250

315

HIVERT-Y/T 06/031

2650

2150×1400×2400

2150×1400×2400

2815×1400×2400

2150×1400×2400

2150×1400×2400

2815×1400×2400

LA1.1

LA1.1P

LA1.1Q

LC1.1

LC1.1P

LC1.1Q

315

400

HIVERT-Y/T 06/040

2760

400

500

HIVERT-Y/T 06/048

2930

450

560

HIVERT-Y/T 06/055

3160

500

630

HIVERT-Y/T 06/061

3360

560

700

HIVERT- Y/T 06/068

3985

3450×1600×2250

3450×1600×2250

4115×1600×2250

3450×1600×2250

3450×1600×2250

4115×1600×2250

LA2.1

LA2.1P

LA2.1Q

LC2.1

LC2.1P

LC2.1Q

630

800

HIVERT- Y/T 06/077

4042

710

890

HIVERT- Y/T 06/086

4160

800

1000

HIVERT- Y/T 06/096

4382

900

1150

HIVERT- Y/T 06/109

4590

1000

1250

HIVERT- Y/T 06/130

4792

1120

1400

HIVERT-Y/T 06/135

4985

1250

1600

HIVERT-Y/T 06/154

5285

1250

1600

HIVERT- Y/T 06 /154P

5930

4150×1600×2250

4150×1600×2250

4815×1600×2250

4150×1600×2250

4150×1600×2250

4815×1600×2250

LA3.1

LA3.1P

LA3.1Q

LC3.1

LC3.1P

LC3.1Q

 

 

 

 

Specification of 6kV/560-6600kw General Medium Voltage Drive

Item

Parameters

VFD rated power

210~28000kVA※

Rated voltage

3.3kV~11kV(-20%~+5%)※(Out of range, special instructions required)

Rated Frequency

50Hz/60Hz(-10%~+10%)※

Control Power

380VAC, 30kVA

Rated input power factor

≥0.96

Effciency

>96%

Output frequency range

0~80Hz※

Speed accuracy

±0.5%(Open loop vector) ±0.1%(close loop vector)

Instantaneous over-current protection

150%( Can be customized according to user requirements)

Over capacity

120% load for 120s

Torque limitation

10%~150%

Analog input

3 ways 4~20mA/Excitation feedback 4~20mA(Customized)

Analog output

4ways 4~20mA

Host communication

Isolated RS485 interface, ModBus RTU, Profibus DP(optional), Industry Ethernet

Acceleration and deceleration time

5s~6000s ( related to load)

DI

14 inputs/22 outputs (Output 8 ways can be defined)

Environment temperature

-5~+45℃※

Storage/transportation temperature

-25~+55℃※

Cooling methord

Air forced cooling (AF) / Water cooled (WF)/Air forced water cooled (AFWF)

Humidity

<95%, no condensation

Altitude

≤1000m, when altitude is higher than 1000m, each 100 meter increasing needs 1%

derating of VFD

Dust

Non-conductive, no causticity, <6.5mg/dm3※

Protection level

IP30※

Cabinet colors

RAL 7032(customized)

https://www.hiconics-global.com/products/6kv-560-6600kw-general-medium-voltage-drive.html