• $100000

6kV/630~12500kW Water-cooled Medium Voltage Drive

Whatever your industry is, Hiconics’s medium voltage drive could be an all-rounder to control your standard applications and optimize your processes. Tailor the drive to your specific application by selecting from an extended choice of pre-engineered options. Extensive versatility makes our VFD suitable for operations in different conditions and environments, even hazardous areas. High reliability in your daily business is ensured by the drive’s simple design and robust control platform that has proven itself over many years.

Technical Parameters of 6kV/630~12500kW Water-cooled Medium Voltage Drive

Voltage

Motor Power(KW)

Output Capacity(KVA)

Model

Weight

(kg)

Dimension

(W*H*D)

Cabinet Type

6kV

630

800

HIVERT-Y/T 06/077W

5450

5000×1200×2200

5800×1200×2200

LAW2.1

LCW2.1

800

1000

HIVERT-Y/T 06/096W

5600

1000

1250

HIVERT-Y/T 06/130W

5800

1250

1600

HIVERT-Y/T 06/154W

7050

5850×1200×2300

LAW3.1

1400

1800

HIVERT-Y/T 06/173W

7350

1600

2000

HIVERT- Y/T 06/192W

7660

1800

2250

HIVERT- Y/T 06/220W

7960

2000

2500

HIVERT- Y/T 06/243W

8310

2250

2800

HIVERT- Y/T 06/275W

10410

7500×1400×2400

7870×1400×2400

LAW4.1

LCW4.1

2500

3200

HIVERT- Y/T 06/304W

10760

2800

3500

HIVERT- Y/T 06/340W

11170

3200

4000

HIVERT-Y/T 06/400W

11700

3600

4500

HIVERT-Y/T 06/425W

15240

9300×1600×2400/2800

9700×1600×2400/2800

LAW5.1

LCW5.1

4000

5000

HIVERT- Y/T 06 /500W

15790

 

 

 

Specification of 6kV/630~12500kW Water-cooled Medium Voltage Drive

Item

Parameters

VFD rated power

210~28000kVA※

Rated voltage

3.3kV~11kV(-20%~+5%)※(Out of range, special instructions required)

Rated Frequency

50Hz/60Hz(-10%~+10%)※

Control Power

380VAC, 30kVA

Rated input power factor

≥0.96

Effciency

>96%

Output frequency range

0~80Hz※

Speed accuracy

±0.5%(Open loop vector) ±0.1%(close loop vector)

Instantaneous over-current protection

150%( Can be customized according to user requirements)

Over capacity

120% load for 120s

Torque limitation

10%~150%

Analog input

3 ways 4~20mA/Excitation feedback 4~20mA(Customized)

Analog output

4ways 4~20mA

Host communication

Isolated RS485 interface, ModBus RTU, Profibus DP(optional), Industry Ethernet

Acceleration and deceleration time

5s~6000s ( related to load)

DI

14 inputs/22 outputs (Output 8 ways can be defined)

Environment temperature

-5~+45℃※

Storage/transportation temperature

-25~+55℃※

Cooling methord

Air forced cooling (AF) / Water cooled (WF)/Air forced water cooled (AFWF)

Humidity

<95%, no condensation

Altitude

≤1000m, when altitude is higher than 1000m, each 100 meter increasing needs 1%

derating of VFD

Dust

Non-conductive, no causticity, <6.5mg/dm3※

Protection level

IP30※

Cabinet colors

RAL 7032(customized)