XLPE Insulated Power Cable

XLPE Insulated Power Cable

Product Description

Application : This product is suitable for transmission and distribution system at the voltage from LV to MV. The power cables can be flame retardant when used as type ZR.

Installation Temperature : The installation temperature should be over 0C . If the ambient temperature is lower than 0C,the cable should be preheated.

Operating Temperature : Max permissible continuous operating temperature of conductor shall not exceed 90C .

Conductor Short-circuit Temperature : Max temperature at short-circuit shall not exceed 250C . The short-circuit duration shall not exceed 5 seconds.

Bending Radius: 20( d+D) +/-5% for single core cable,15( d+D )+/-5% for multi-core cable.

D=Actual outer diameter of cable (mm),d=Actual diameter of the conductor (mm)

Standard: IEC60502, GB/T12706 or other standard required by customer. The requirements for flame retardant property is according to IEC60332-3 and GB18380.

Packing: Steel/wooden reel, wooden reel or steel reel.

Supply Range

Type

No of

Cores

Rated Voltage (kV)

0.6/1

3.6/6

6/6

6/10

8.7/10 8.7/15

12/20

21/35

26/35

26/45

Nominal Area of Conductor (sq.mm)

CU or AL/XLPE/PVC

1

1.5 to 240

25 to 500

25 to 500

25 to 500

35 to 500

50 to 500

50 to 500

3

1.5 to 240

25 to 300

25 to 300

25 to 300

35 to 300

CU or

AL/XLPE/STA/PVC

3

10 to 240

25 to 300

25 to 300

25 to 300

35 to 300

CU or

AL/XLPE/SWA/PVC

3

10 to 240

25 to 300

25 to 300

25 to 300

35 to 300