Rubber Pipe Insulation

 

Rubber Pipe Insulation

Shenzhou Class O/Class 1 Rubber Pipe Insulation is a kind of flexible insulation material with completely closed cell, whichis mainly made of nitrile but a diene rubber. The product has excellent thermal performance. Foam Rubber Insulation Pipes are widely used invarious public places, industrial plants,clean rooms,medical scenes, education scenes and others cenes.

Closed Cell Rubber Pipe Insulation

Closed Cell Rubber Pipe Insulation is a flexible, lightweight elastomeric thermal insulation material designed for insulating chilled water lines, heating pipes, ductwork, tanks, and vessels. Its expanded closed-cell structure forms an effective vapor barrier that prevents condensation (“sweating”) on cold pipelines and helps avoid frost formation in refrigeration and chilled water systems. At the same time, it efficiently reduces heat loss in hot piping systems.

Thanks to its dense surface layer and closed-cell structure, the material maintains stable thermal conductivity during long-term service. Rubber Insulation for Pipes provides a fast, efficient, and reliable solution for pipe insulation in HVAC, plumbing, hot water heating, air conditioning, and refrigeration systems. It is highly flexible and easy to install on both pipes and tubing.

In addition to thermal performance, the Rubber Insulation for Pipes also helps protect pipes against corrosion and acts as a vibration dampener. A light talcum powder coating on the inner surface supports easier installation and faster pre-assembly in production or on-site applications.

Installation RecommendationsRubber Foam Pipe and Tubing Installation

Suitable for Tube Sizes

Inside Diameter

Insulation Wall Thickness(mm)

(in) Outer Diameter of Copper Pipe

(DN) Galvanized Pipe Nominal

(mm) Seamless Pipe Outside Diameter

(mm) Rubber Foam Inside Diameter

9

15

20

25

32

40

50

1/4 “

— —

— —

6

6X9 10X9 13X9 16X9 19X9 22X9 25X9 27X9 32X9 34X9 38X9 43X9 48X9 57X9 60X9

6X15 10X15 13X15 16X15 19X15 22X15 25X15 27X15 32X15 34X15 38X15 43X15 48X15 57X15 60X15 76X15 89X15 108X15

6X20 10X20 13X20 16X20 19X20 22X20 25X20 27X20 32X20 34X20 38X20 43X20 48X20 57X20 60X20 76X20 89X20 108X20

13X25 16X25 19X25 22X25 25X25 27X25 32X25 34X25 38X25 43X25 48X25 57X25 60X25 76X25 89X25 108X25

16X32 19X32 22X30 25X32 27X32 32X32 34X32 38X32 43X32 48X32 57X30 60X30 76X30 89X30 108X30

25X40 27X40 32X40 34X40 38X40 43X40 48X40 57X30 60X30 76X30 89X30 108X30

25X50 27X50 32X50 34X50 38X50 43X50 48X50 57X30 60X30 76X30 89X30 108X30

3/8 “

6

— —

10

1/2 “

— —

— —

13

5/8 “

8

14

16

3/4 “

— —

— —

19

7/8 “

15

22

22

1 “

— —

25

25

1-1/8 “

20

28

28

1-1/4 “

— —

32

32

— —

— —

— —

34

1-1/2 “

 

38

38

1-5/8 “

32

— —

43

1-7/8 “

40

— —

48

2-1/4 “

— —

57

57

2-3/8 “

50

— —

60

— —

70

76

76

— —

80

89

89

— —

 

108

108

Test Items

Length(m)

Width(m)

Area(m2)

10mm

20

1

20

15mm

10

1.2

12

8

1.5

20mm

10

1.2

8

1.5

25mm

10

1.2

8

1.5

30mm

10

1.2

8

1.5

Test Items

Performance Indicators

Compliance Standards

Density

≤95 kg/m3

GB/T 6343-2009

Service Temperature

-40℃ to 105℃

 

Thermal Conductivity

Average Temp.

-20℃

0℃

+25℃

GB/T 10294-2008 ASTM C518 ASTM C177

W/m.K

0.032

0.034

0.036

Water Vapour Permeability

< 4.0 x 10-11g/(m.s.Pa) u ≥4500

GB/T 17146-2015

Water Absorption by Volume

≤0.50%

GB/T 17794-2021

Reaction to Fire

B1 grade(C-s3,d0,t1)

GB 8624-2012

Class 1

BS 476-7

V-0,sVA/ HF-1,Self Extinguishing,Does not Drip

UL94

Oxygen Index

≥32

GB/T 2406-2008

Smoke Density Class

≤75

GB/T 8627-2007

Compression Rebound Rate

≥ 70%

GB/T 6669-2001

Dimension Stability

≤10.0%

GB/T 8811-2008

Aging Resistance

Slightly Crumpling, No cracks, No pin holes, Not deforming

GB/T 16259-2008

Ozone Resistance Corrosion Resistance Environment

Good No Corrosion Dust and Fibre Free CFC Free, Tero ODP, Zero GWP

 

Closed cell rubber foam pipe insulation provides a quick and efficient method for insulating refrigeration, cooling, and heating pipelines. Installation should be carried out on dry, clean, and unheated pipes.

Two main installation methods are commonly used:

– · Slip-on method: used for new pipes before installation or system assembly

– · Snap-on method: used for existing installed piping systems

The tubing can be easily cut and shaped for fittings such as elbows, tees, and bends. For threaded fittings, sleeve covers should be made using insulation of the same thickness as the pipe, ensuring proper overlap with the existing insulation layer.

It is important not to compress the rubber foam insulation material, as this may reduce its thermal performance and lead to condensation risks. Always select the correct size, avoid stretching, and ensure full coverage without tension. All seams and joints should be properly sealed to maintain insulation integrity.

– · HVAC engineering and contracting

– · Construction and building services

– · Petrochemical and industrial plants

– · Cold storage and refrigeration industries

– · Shipbuilding and marine systems